- From: Fredrik Lingvall <fl_at_signal.uu.se>
- Date: Wed, 27 Nov 2002 14:29:52 +0100
Frank Mori Hess wrote: > >Fredrik, > >Did you use scan_begin_src TRIG_TIMER or TRIG_FOLLOW, and does single channel >work either way? > This it the command setup that I used: cmd->start_src = TRIG_NOW; cmd->start_arg = 0; cmd->scan_begin_src = TRIG_TIMER; cmd->scan_begin_arg = (unsigned int) (1e9/fs); /* in ns */ cmd->convert_src = TRIG_TIMER; cmd->convert_arg = 1; /* in ns */ cmd->scan_end_src = TRIG_COUNT; cmd->scan_end_arg = n_chans; // Number of channels. cmd->stop_src = TRIG_COUNT; cmd->stop_arg = n_scans; cmd->chanlist = chanlist; cmd->chanlist_len = n_chans; Tried: can_begin_src = TRIG_FOLLOW; Now one channel works too (great!), but if I use several channels the order must still be consecutive. Fredrik
Received on 2002-11-27Z13:29:52