Re: INT_TRIG for scans...

On 06/06/2007 21:05, Paulo André Capellari wrote:
> Hello for all!
> 
> I'm new here and want a newby information ;)
> 
> I've seen the use of INT_TRIG to start an "aquisition", but I'm looking 
> for something like this to start a "scan"... someone can help-me?
> 
> thanks!

I don't think any of the drivers support using a software trigger to 
start a "scan", but most (?) of them support starting an "acquisition" 
that way.

You could configure the acquisition to stop after one scan (stop_src = 
TRIG_COUNT, stop_arg = 1) and set up the acquisition again each time it 
completes.

-- 
-=( Ian Abbott _at_ MEV Ltd.    E-mail: <abbotti_at_mev.co.uk>        )=-
-=( Tel: +44 (0)161 477 1898   FAX: +44 (0)161 718 3587         )=-

Received on 2007-06-13Z08:14:24