---------- Forwarded message ---------- From: Paulo André Capellari <paulo.capellari_at_gmail.com> Date: 13/06/2007 13:10 Subject: Re: INT_TRIG for scans... To: Ian Abbott <abbotti_at_mev.co.uk> hello! I'm working on it, but if I start "multiple commands" only the first is executed, can you explain why? thanks 2007/6/13, Ian Abbott < abbotti_at_mev.co.uk>: > > On 06/06/2007 21:05, Paulo André Capellari wrote: > > Hello for all! > > > > I'm new here and want a newby information ;) > > > > I've seen the use of INT_TRIG to start an "aquisition", but I'm looking > > for something like this to start a "scan"... someone can help-me? > > > > thanks! > > I don't think any of the drivers support using a software trigger to > start a "scan", but most (?) of them support starting an "acquisition" > that way. > > You could configure the acquisition to stop after one scan (stop_src = > TRIG_COUNT, stop_arg = 1) and set up the acquisition again each time it > completes. > > -- > -=( Ian Abbott _at_ MEV Ltd. E-mail: <abbotti_at_mev.co.uk> )=- > -=( Tel: +44 (0)161 477 1898 FAX: +44 (0)161 718 3587 )=- > -- Paulo André Ciência da Computação - Unioeste/PTI -- Paulo André Ciência da Computação - Unioeste/PTI